2 Hardware Specifications and Wiring 2.1 Hardware Specifications This chapter only provides information on electrical specification and wiring. For detailed information on program design and instructions, please refer to Chapter 5 ~ 6. For how to purchase its peripheral devices, please refer to the instruction sheet enclosed with the product. 2.1.1 Electrical Specifications 2.1.2 I/O Point Specifications Input point specifications:
„ DVP20PM00D DVP-PM Application Manual 2-1 20PM 10PM Power supply 100 ~ 240V AC(-15% ~ 10%), 50/60Hz ± 5% voltage Power supply fuse 2A/250VAC Power consumption 60VA DC24V current 500mA output Power supply DC24V; output short-circuit protection protection Voltage withstand 1,500VAC (Primary-secondary); 1,500VAC (Primary-PE); 500VAC (Secondary-PE) Insulation > 5MΩ (all I/O point-to-ground: 500VDC) resistance ESD: 8KV Air Discharge; EFT: Power Line: 2KV, Digital I/O: 1KV, Analog & Communication Noise immunity I/O: 250V The diameter of grounding wire shall not be less that of L, N terminal of the power.
(When Grounding many PLCs are in use at the same time, please make sure every PLC is properly grounded.) Operation: 0°C ~ 55°C (temperature), 50 ~ 95% (humidity), pollution degree 2 Environment Storage: -25°C ~ 70°C (temperature), 5 ~ 95% (humidity) Vibration/shock International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 resistance (TEST Ea) Weigh (approx. g.) 478/688 Max.
input Response Terminal Description time Current Voltage START0, START1 For input signals of Start 10ms 6mA 24V STOP0, STOP1 For input signals of Stop 10ms 6mA 24V LSP0/LSN0, 24V Right limit input/left limit input 10ms 6mA LSP1/LSN1 MPG A-phase pulse input +, - (differential signal 5 ~ 24V A0+, A0-, A1+, A1- 200kHz 15mA input) (A1+, A1- are shared by Y and Z ) MPG B-phase pulse input +, - (differential signal 5 ~ 24V B0+, B0-, B1+, B1- 200kHz 15mA input) (B1+, B1- are shared by Y and Z)