5 Categories and Use of Basic Application Instructions API 11 Operands: S 1 : Lower bound of zone comparison S 2 : Upper bound of zone comparison S : Comparison value D : Comparison result Explanations: 1. S is compared with its lower bound S 1 and upper bound S 2 and D stores the comparison results. 2. ZCP instruction supports V and Z. When ZCP is used as 16-bit instruction, Z device cannot be adopted; when ZCP is used as 32-bit instruction, V device cannot be adopted. 3. Operand S 1 should be smaller than operand S 2. When S 1 > S 2 , the instruction takes S 1 as the 1 st comparison 4. Operand D occupies 3 consecutive devices.
D , D +1, D +2 hold the comparison results, D = ON if S 1 > S , D +1 value and performs normal comparison similar to CMP instruction. = ON if S 1 ≦ S ≦ S 2 , D +2 = ON if S 2 S . Program Example: 1. If D is set as M0, then M0, M1, M2 will work as the program example below. 2. When X0 = ON, ZCP instruction is driven and one of M0, M1, M2 is ON. When X0 = OFF, ZCP instruction is not driven and M0, M1, M2 remain in the previous status. X0 3.
Use RST or ZRST instruction to reset the comparison results DVP-PM Operation Instruction 5-24 Mnemonic Operands Function Controllers 20PM 10PM D ZCP P Zone Compare Type OP Bit Devices Word Devices Program Steps X Y M S K H KnX KnY KnM KnS T C D V Z ZCP, ZCPP: 9 steps DZCP, DZCPP: 12 steps S 1 * * * * * * * * * * * D S 2 * * * * * * * * * * * S * * * * * * * * * * * D * * * ZCP K10 K100 C10 M0