Delta Electronics — 5.6 Application Instructions

5 Categories and Use of Basic Application Instructions API 25 Operands: D : Destination device Explanations: 1. If the instruction is not used in pulse execution mode, the content in the designated device D will minus “1” in every scan period. 2. When DEC is executed, the content in D will be decremented. However, in 16-bit instruction, if –32,768 is reached and “1” is minused, it will write a value of +32,767 to the destination. In 32-bit instruction, if -2,147,483,648 is reached and “1” is minused, it will write a value of +2,147,483,647 to the destination 3.

When DEC is used as 16-bit instruction, Z device cannot be adopted; when DEC is used as 32-bit instruction, V device cannot be adopted. 4. This instruction is generally used in pulse execution mode (DEC P, DDEC P) Program Example: When X0 is triggered, the value in D0 will be decremented by 1. X0 DVP-PM Operation Instruction 5-42 Mnemonic Operands Function Controllers 20PM 10PM D DEC P Decrement Type OP Bit Devices Word Devices Program Steps X Y M S K H KnX KnY KnM KnS T C D V Z DEC, DECP: 3 steps DDEC, DDECP: 3 steps D * * * * * * * * D DECP D0