Mitsubishi — 5.6 Application Instructions

5 Categories and Use of Basic Application Instructions Operands: S : Start No. of source device D : Start No. of destination device n 1 : Length of data to be shifted n 2 : Number of bits to be shifted as a group Explanation: 1. This instruction performs a right shift from source device of n 2 bits starting from S to destination device of n 1 bits starting from D. 2. This instruction is generally used in pulse execution mode (SFTRP). 3. When SFTR is used as 16-bit instruction, Z device cannot be adopted; when SFTR is used as 32-bit instruction, V device cannot be adopted. 4. Valid range of operand n1 , n2 : 1≤ n2 ≤ n1 ≤1024 Program Example: 5.

When X0 is rising edge triggered, SFTR instruction shifts X0~X4 into 16 bit data M0~M15 and M0~M15 also shift to the right with a group of 4 bits. 6. The figure below illustrates the right shift of the bits in one scan. n M3~M0 → Carry o M7~M4 → M3~M0 p M11~M8 → M7~M4 q M15~M12 → M11~M8 r X3~X0 → M15~M12 completed X0 4 bits in a group shift to the right 5 Carry 1 2 3 4 DVP-PM Operation Instruction 5-52 API Mnemonic Operands Function Controllers 20PM 10PM 34 SFTR P Bit Shift Right Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY Kn M KnS T C D E F SFTR, SFTRP:

9 steps S * * * * D * * * n 1 * * n 2 * * SFTR X0 M0 K16 K4 X3 X2 X1 X0 M15 M1 4 M13 M12 M11 M1 0 M9 M8 M 7 M6 M5 M4 M3 M2 M1 M0