5 Categories and Use of Basic Application Instructions Operands: S : Source device to be encoded D : Device for storing the result n : Number of consecutive bits of S Explanation: 1. The instruction encodes the lower “2 n ” bits of source S and stores the result in D . 2. They highest active bit in S has the priority for encoding operation. 3. When ENCO is used as 16-bit instruction, Z device cannot be adopted; when ENCO is used as 32-bit instruction, V device cannot be adopted. 4. This instruction is generally used in pulse execution mode (ENCOP). 5. When operand S is a bit device, n =1~8, when operand S is a word device, n =1~4 6.
If no bits in S is active (1), M1067, M1068 = ON and D1067 records the error code 0E1A (hex). Program Example 1: 1. When S is used as a bit device, n = 1 ~ 8. Errors will occur if n = 0 or n > 8. 2. f n = 8, the decoded data is 2 8 = 256 bits data. 3. When X0 goes from OFF to ON, the data in (M0 to M7) will be encoded and stored in lower 3 bits of D0 (b2 to 4. After the execution is completed, X0 is turned OFF and the data in D remains unchanged. b0). The unused bits in D0 (b15 to b3) will be set to 0. X0 M7 M6 M5 M4 M3 M2 M1 M0 b15 b0 D0 Program Example 2: 1. When S is used as a word device, n = 1 ~ 4. Errors will occur if n = 0 or n > 4. 2.
When n = 4, the decoded data is 2 4 = 16 bits data. 3. When X0 goes from OFF to ON, the 2 3 bits (b0 ~ b7) in D10 will be encoded and the result will be stored in the lower 3 bits of D20 (b2 to b0). The unused bits in D20 (b15 to b3) will be set to 0. 4. After the execution is completed, X0 is turned OFF and the data in D remains unchanged X0 DVP-PM Application Manual 5-61 API Mnemonic Operands Function Controllers 20PM 10PM 42 ENCO P Encode Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F DECO, DECOP: 7 steps S * * * * * * * * * D * * * * * n * * ENCOP M0 D0 K3 0 0 0 0 1 0 0 0 7 6 5 4 3 2 1 0 all be 0 4 2 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 ENCOP D10 D20 K3