5 Categories and Use of Basic Application Instructions API 46 Operands: S : Alarm timer m : Time setting D : Alarm Explanations: 1. ANS instruction is used to drive the output alarm device in designated time. 2. Operand S valid range: T0~T183 Operand m valid range: K1~K32,767 (unit: 100 ms) Operand D valid range: S912~S1023 3. Flag: M1048 (ON: Alarm is active), M1049 (ON: Alarm monitoring is enabled) 4. See ANR instruction for more information Program Example: If X3 = ON for more than 5 sec, alarm step relay S999 will be ON. S999 will remains ON after X3 is reset.