5 Categories and Use of Basic Application Instructions Operands: D : Destination device Explanations: 1. The status of D is alternated every time when the ALT instruction is executed. 2. When ALT instruction is executed, ON/OFF state of D will be switched which is usually applied on switching two operation modes, e.g. Start/Stop 3. This instruction is generally used in pulse execution mode (ALTP). Program Example 1: When X0 goes from OFF to ON, Y0 will be ON. When X0 goes from OFF to ON for the second time, Y0 will be OFF. X0 X0 Y0 Program Example 2:
Creating a flashing circuit by applying ALTP with a timer When X20 = ON, T0 will generate a pulse every two seconds and output Y0 will be switched between ON and OFF by the pulses from T0. X20 T0 DVP-PM Application Manual 5-75 API Mnemonic Operands Function Controllers 20PM 10PM 66 ALT P Alternate State Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F ALT, ALTP: 3 steps D * * * ALTP Y0 TMR T0 K20 T0 ALTP Y0 TMR T0 K20 ALTP Y0