Mitsubishi — 5.6 Application Instructions

5 Categories and Use of Basic Application Instructions Adjust the D/A conversion curve of DVP02DA-H2. Set the OFFSET value of CH2 as 0mA ( = K0 LSB ) and GAIN value as 10mA ( = K1,000 LSB ). M1002 X0 1. Write H’18 into CR#1 of analog output module No. 1 to set CH2 as mode 3 (current output: 0mA ~ +20mA). 2. Write H’0 into CR#33 to allow OFFSET/GAIN tuning in CH1 and CH2. 3. When X0 goes from OFF to ON, write the OFFSET value K0 LSB into CR#22 and the GAIN value K1,000 LSB into CR#28. FROM/TO Application Example 4: Adjust the D/A conversion curve of DVP02DA-H2. Set the OFFSET value of CH2 as 2mA ( = K400 LSB ) and GAIN value as 18mA ( = K3,600 LSB ) . 1.

Write H’10 to CR#1 of analog output module No. 1 to set CH2 as mode 2 (current output: +4mA ~ +20mA). 2. Write H’0 to CR#33 to allow OFFSET/GAIN tuning in CH1 and CH2. 3. When X0 goes from OFF to ON, write the OFFSET value K400 LSB into CR#23 and GAIN value K3,600 LSB into CR#29. DVP-PM Application Manual 5-83 TO K1 K1 H18 K1 TO K1 K33 H0 K1 TO K1 K22 K0 K1 TO K1 K28 K1000 K1 M1002 TO K1 K1 H10 K1 TO K1 K33 H0 K1 X0 TO K1 K23 K400 K1 TO K1 K29 K3600 K1 TO K1 K29 K3600 K1 TO K1 K1 H10 K1 TO K1 K33 H0 K1 TO K1 K23 K400 K1