5 Categories and Use of Basic Application Instructions DVP-PM Ц VFD-B, DVP-PM transmits: “ 01 03 2101 0006 D4 ” VFD-B Ц DVP-PM, DVP-PM receives: “ 01 03 0C 0100 1766 0000 0000 0136 0000 3B ” Registers for data to be sent (sending messages) Registers for received data (responding messages) 0136 H DVP-PM Operation Instruction 5-86 Register DATA Explanation D1089 low ‘0’ 30 H ADR 1 ADR 0 Address of AC motor drive: ADR (1,0) D1089 high ‘1’ 31 H D1090 low ‘0’ 30 H CMD 1 CMD 0 Command code:
CMD (1,0) D1090 high ‘3’ 33 H D1091 low ‘2’ 32 H Starting Data Address D1091 high ‘1’ 31 H D1092 low ‘0’ 30 H D1092 high ‘1’ 31 H D1093 low ‘0’ 30 H Number of Data (count by word) D1093 high ‘0’ 30 H D1094 low ‘0’ 30 H D1094 high ‘6’ 36 H D1095 low ‘D’ 44 H LRC CHK 1 LRC CHK 0 Checksum:
LRC CHK (0,1) D1095 high ‘4’ 34 H Register DATA Explanation D1070 low ‘0’ 30 H ADR 1 ADR 0 D1070 high ‘1’ 31 H D1071 low ‘0’ 30 H CMD 1 CMD 0 D1071 high ‘3’ 33 H D1072 low ‘0’ 30 H Number of Data (count by byte) D1072 high ‘C’ 43 H D1073 low ‘0’ 30 H Content of address 2101 H 0100 H PLC automatically converts ASCII codes and store the converted value in D1050 D1073 high ‘1’ 31 H D1074 low ‘0’ 30 H D1074 high ‘0’ 30 H D1075 low ‘1’ 31 H Content of address 2102 H 1766 H PLC automatically converts ASCII codes and store the converted value in D1051 D1075 high ‘7’ 37 H D1076 low ‘6’ 36 H D1076 high ‘6’ 36 H D1077 low ‘0’ 30 H Content of address 2103 H 0000 H PLC automatically converts ASCII codes and store the converted value in D1052 D1077 high ‘0’ 30 H D1078 low ‘0’ 30 H D1078 high ‘0’ 30 H D1079 low ‘0’ 30 H Content of address 2104 H 0000 H PLC automatically converts ASCII codes and store the converted value in D1053 D1079 high ‘0’ 30 H D1080 low ‘0’ 30 H D1080 high ‘0’ 30 H D1081 low ‘0’ 30 H Content in address