Mitsubishi — 5.6 Application Instructions

5 Categories and Use of Basic Application Instructions Program Example 3: 1. In the communication between DVP-PM and VFD-B series AC motor drive (ASCII Mode, M1143 = OFF), executes Retry when communication time-out, data receiving error or parameter error occurs. 2. When X0 = ON, DVP-PM will read the data of address H2100 in device 01(VFD-B) and stores the data in ASCII format in D1070 ~ D1085. PLC will automatically convert the data and store them in D1050 ~ D1055. 3. M1129 will be ON when communication time-out occurs. The program will trigger M1129 and send request for reading the data again. 4. M1140 will be ON when data receiving error occurs.

The program will trigger M1140 and send request for reading the data again. 5. M1141 will be ON when parameter error occurs. The program will trigger M1141 and send request for reading the data again. M1002 Set communication protocol as 9600, 8, E, 1 Retain communication protocol Set communication time-out as 100ms X0 Sending request M1129 M1140 Retry when communication time-out occurs Retry when data receiving error occurs M1141 Retry when parameter error occurs X0 Set communication instruction: Data address: Data length: 6 words H2100 Device address:

01 Receiving completed M1127 Handle received data The received ASCII data is stored in D1070-D1085 and PLC converts the data and store them into D1050-D1055 automatically. Reset M1127 M1129 Reset M1129 (receiving timeout) Points to note: 1. Rising-edge contact (LDP, ANDP, ORP) and falling-edge contact (LDF, ANDF, ORF) can not be used with MODRD instruction, otherwise the data stored in the receiving registers will be incorrect. 2. There is no limitation on the times of using this instruction, but only one instruction can be executed at a time.

DVP-PM Operation Instruction 5-88 D1071 low 03 H Command code of AC motor drive D1072 low 04 H Number of data (count by byte) D1073 low 17 H Content of address 2102 H D1074 low 70 H D1075 low 00 H Content of address 2103 H D1076 low 00 H D1077 low FE H CRC CHK Low D1078 low 5C H CRC CHK High MOV H87 D1120 SET M1120 MOV K100 D1129 SET M1122 MODRD K1 H2100 K 6 RST M1127 RST M1129