Mitsubishi — 5.6 Application Instructions

5 Categories and Use of Basic Application Instructions DVP-PM Ц VFD-B, DVP-PM transmits: “ 01 06 0100 1770 71 ” VFD-B Ц DVP-PM, DVP-PM receives: “ 01 06 0100 1770 71 ” Registers for data to be sent (sending messages) Registers for received data (responding messages) DVP-PM Operation Instruction 5-90 Register DATA Explanation D1089 low ‘0’ 30 H ADR 1 ADR 0 Address of AC motor drive: ADR (1,0) D1089 high ‘1’ 31 H D1090 low ‘0’ 30 H CMD 1 CMD 0 Command code of AC motor drive:

CMD (1,0) D1090 high ‘6’ 36 H D1091 low ‘0’ 30 H Data Address D1091 high ‘1’ 31 H D1092 low ‘0’ 30 H D1092 high ‘0’ 30 H D1093 low ‘1’ 31 H Data contents D1093 high ‘7’ 37 H D1094 low ‘7’ 37 H D1094 high ‘0’ 30 H D1095 low ‘7’ 37 H LRC CHK 1 LRC CHK 0 Checksum: LRC CHK (0,1) D1095 high ‘1’ 31 H Register DATA Explanation D1070 low ‘0’ 30 H ADR 1 ADR 0 D1070 high ‘1’ 31 H D1071 low ‘0’ 30 H CMD 1 CMD 0 D1071 high ‘6’ 36 H D1072 low ‘0’ 30 H Data Address D1072 high ‘1’ 31 H D1073 low ‘0’ 30 H D1073 high ‘0’ 30 H D1074 low ‘1’ 31 H Data content D1074 high ‘7’ 37 H D1075 low ‘7’ 37 H D1075 high ‘0’ 30 H D1076 low ‘7’ 37 H LRC CHK 1 LRC CHK 0 D1076 high ‘1’ 31 H