Mitsubishi — 9.4.2.2 Smooth Curve Interpolation

9 Electrical CAM (a) Multiple-point E-CAM Data or no data (b) 3-point E-CAM Data Control Steps: Step 1: Set M80 to convert the 4-point E-CAM data (3-point data with an additional point 0) into binary floating point format, and store the results in D0~D15. Step 2: Set M81 to to write the data in D0~D15 into E-CAM chart-0 (K100). Step 3: Set M82 to read the written data back into D100~D115 so as to confirm the data is correctly written into E-CAM chart-0. Step 4: Use Monitor Table to confirm the data read back in D100~D115. Data format (Radix) of D100~D115 should be set as floating point. Ladder Diagram:

M80 M81 M82 9.4.2.2 Smooth Curve Interpolation DVP-PM Application Manual 9-34 DFLT K0 D0 DFLT K0 D2 DFLT K16000 D4 DFLT K10000 D6 DFLT K32000 D8 DFLT K0 D10 DFLT K0 D12 DFLT K0 D14 DTO K100 K0 D0 K8 DFROM K100 K0 D100 K8