2 Hardware Specifications and Wiring 2.3 Communication Ports DVP-PM offers two built-in communication ports, COM1 (RS-232 communication) COM2 (RS-485 communication) and one optional communication card, COM3 (RS-232/RS485.communication) COM1: RS-232 communication port. Main communication port for programming. Can be used as Slave in Modbus ASCII or RTU mode. COM2: RS-485 communication port. Can be used as Slave / Master in Modbus ASCII or RTU mode. COM3: RS-232/RS-485 communication port. Can be used as Slave in Modbus ASCII mode. Communication Format: Default communication settings: − Modbus ASCII − 7 bits − 1 stop bit − EVEN parity − Baud rate: 9600bps 2.3.1 COM1 (RS-232) 1.
COM1 supports RS-232 data transmission which uploads and downloads PLC program. The communication format is Modbus (ASCII/RTU mode) and the baud rate is 9,600 ~ 115, 200bps. Communication cable(DVPACAB2A30):
DVP-PM Application Manual 2-28 COM port RS-232 RS-485 RS-232/RS-485 Parameter (COM1) (COM2) (COM3) Baud rate 110~115,200 bps 110~38,400 bps Data length 7~8bits Parity Even/Odd/None parity check Length of stop bit 1~2 bits Register for Setting D1036 D1120 D1109 Available for Slave Available for Master/Slave Available for Slave ASCII mode Available for Slave Available for Master/Slave - RTU mode Data length for access 100 registers 32 registers (ASCII) Data length for access 100 registers 32 registers (RTU)