3 Functions of Devices in DVP-PM The handling process of DVP-PM program: Update input signal ѓ Update input signal X input 1. Before the execution of the program, DVP-PM reads the ON/OFF status of the external input signals into the input signal memory. 2. The ON/OFF status of input signal changed during program execution will not be read into input signal Program processing memory. The new ON/OFF status will be read in the 3. There will be approximately a 10ms delay from external next scan. ON/OFF switching to the internal ON/OFF of contacts. The delay time may be affected by program scan time.
ѓ Program processing Update output After DVP-PM reads the ON/OFF status stored in the input signal memory, it executes every instruction from address 0 and stores the status of devices into the device memory. ѓ Update output Y output 1. When the execution reaches M102 instruction, DVP-PM sends the ON/OFF status of Y in the device memory to the output latched memory. The output latched memory is the coil of the output relay. 2. There will be a 10ms delay from the ON/OFF switching of output relay to the actual ON/OFF of physical output contacts. 3. For transistor output MPU, there will be a 10 ~ 20us delay from the ON/OFF switching to the actual ON/OFF of physical output contacts.
3.4 Numbering and Functions of Auxiliary Relays [M] ѓ No. of auxiliary relays (in decimal): ѓ Functions of auxiliary relays: Both auxiliary relay M and output relay Y have output coils and NO, NC contacts, and there is no limitation on the times of using the contacts. You can use auxiliary relay M in the program but it cannot directly drive the external load. There are three types of auxiliary relays.
DVP-PM Application Manual 3-7 Input terminal Read into m Input signal memory sing Read X0 status from 0 Write in Y0 status memory Y0 Read Y0 status from memory 0 Device M0 Write in M0 status Output Output latched memory Output terminal eciveD yromem Output latched memory Output terminal General purpose M0 ~ M499, 500 points, can be modified as latched area by setting up parameters. Total 4,096 points Auxiliary relay Latched M500 ~ M999, M3000 ~ M4095, 1,596 points, can be modified as non-latched area by setting up parameters. M Special purpose M1000 ~ M2999, 2,000 points, some are latched.