Mitsubishi — 3.7 Numbering and Functions of Counters [C]

3 Functions of Devices in DVP-PM How to designate SV: The actual set time in the timer = timer resolutiont Ч set value 1. Designating constant K: set a K value as SV directly 2. Designating D register: designate a data register in TMR instruction and the timer will take the value in the register as the SV. 3.7 Numbering and Functions of Counters [C] ѓ No. of counters (in decimal): 20PM: 10PM: ѓ Features of counter: DVP-PM Application Manual 3-9 16-bit count up C0 ~ C199, 200 points The associated contact = ON Total 248 points when counter reaches preset 32-bit count up/down C208 ~ C255, 48 points (accumulative) value Counter z Input point of C200:

C MPGA0/MPGB0 32-bit high speed C200, C204 Total 2 points z Input point of C204: MPGA1/MPGB1 16-bit count up C0 ~ C199, 200 points The associated contact = ON Total 236 points when counter reaches preset 32-bit count up/down C220 ~ C255, 36 points (accumulative) value z Input point of C200: X0/X1 z Input point of C204: Counter X2/X3 z Input point of C208: C C200, C204, C208, C212, C216, C220. X4/X5 32-bit high speed Total 6 points 6 points z Input point of C212: X6/X7 z Input point of C216: X10+ / X10- / X11+ / X11- z Input point of C220:

X12+ / X12- / X13+ / X13- 16-bit counter 32-bit counter Type General purpose General purpose Counting direction Count up Count up, count down Range of SV 0 ~ 32,767 -2,147,483,648 ~ +2,147,483,647 Designating SV Constant K or data register D Constant K or data register D (2 consecutive words) Operation when SV Counting will stop after SV is reached. Counting will continue after SV is reached. is reached The associated contact = ON and latched when counter reaches SV.

The associated contact = ON and latched when counter reaches preset value in counting-up mode The associated contact is reset as OFF when counter reaches preset value in counting-down mode Output contact Reset When RST instruction is executed, PV of counter is cleared and the contact is OFF. Contact Action Contacts act when the scan is completed. Contacts act when the scan is completed.