14 High Speed Compare and Capture Sequential control process: Step 1: Initial setting for high speed Compare when O100 is activated: (1) D0 = 0 Ж Specify the number of the starting set. n = 0 indicates the first set. (2) D1 = 0 (3) D20 = 10 Ж Set up data length for TO instruction: 10 words, including 2 sets of comparison data (4) D60 = 10 Ж Set up data length for FROM instruction: 10 words, including 2 sets of comparison data. Step 2: Set M1. Specify the comparison data in control registers and data registers. (1) Control registers of the 1 st set: D3, D2 = H124 Ж Data source: C204(Bit3-0=4); compare method: ≧ , SET (Bit5-4=2) (Bit7-6=0); output terminal: CLR0 (Bit11-8=1).
(2) Data registers of the 1 st set: D5, D4 = K100 Ж output terminal will be triggered when source value ≧ K100. (3) Control registers of the 2 nd set: D7, D6 = H164 Ж Data source: C204(Bit3-0=4); compare method: ≧ , RST (Bit5-4=2) (Bit7-6=1); output terminal: CLR0 (Bit11-8=1). (4) Data registers of the 2 nd set: D9, D8 = K300 output terminal will be triggered when source value ≧ K300. Step 3: Set M2. Activate the 2 sets of high speed Compare Step 4: Set M3. Read the data set up in D0~D9 as below: Step 5: Set M4 to set C204 counting mode as P/D (Pulse/direction) then set M5 to enable C204. Step 6: Rotate the MPG to check if C204 is counting as below. DVP-PM Application Manual 14-6