Mitsubishi — 15.1 Appendix A: Error Codes

15 Appendix 15.1 Appendix A: Error Codes If error occurs in O100 or OX program area in DVP-PM, the error flag will be ON and ERROR indicator will flash. The causes of errors could be illegal use of instruction operand (device), program syntax error, or improper setting of motion subroutine patameters. Users can monitor the error register and obtain the cause of error according to the error code in error registertrs.

‹ Error codes in all program areas and motion axes & devices for displaying steps ‹ Error codes for program area and motion axis (in hex) DVP-PM Application Manual 14-1 Program area O100 OX Program Motion error Program Motion error Error type error X axis Y axis Z axis error X axis Y axis Z axis Error flag M1953 M1793 M1873 M2033 M1793 M1793 M1873 M2033 Error register D1802 D1857 D1937 D2017 D1857 D1857 D1937 D2017 Number of D1803 D1869 D1869 D1869 error step Code Cause Code Cause 0002 No content in the applied subroutine 0031 Forward pulses prohibited 0003 No corresponding Pn for CJ, CJN, JMP 0032 Reverse pulses prohibited 0004 There is a subroutine flag in main program 0033 Left/right limit achieved 0005 No subroutine 0040 Incorrect use range of device 0006 Repeated index in the same program 0041 MODRD and MODWR communication time-out 0007 Repeated subroutine index 0044 V/Z modification error 0008 Repeated index of jump instructions in different subroutines 0045 Floating point conversion error 0009 JMP instruction and CALL instruction are using the same flag.

0E18 BCD conversion error 000A The index is the same as subroutine index 0E19 Arithmetic error in division (divisor = 0) 0011 Incorrect target position (I) setting C401 General loop error 0012 Incorrect target position (II) setting C402 Continuous use of LD/LDI for more than 9 times 0021 Incorrect running speed (I) setting C404 RPT ~ RPE are used more than 1 layer 0022 Incorrect running speed (II) setting C405 SRET is used between RPT ~ RPE 0023 Incorrect zero return speed (V ) setting RT C4EE There is no end instruction (M102, M2) in the program 0024 Incorrect zerp return deceleration speed (V ) setting CR C4FF No such instruction / Incorrect operand format or incorrect range 0025 Incorrect JOG speed setting