3 Functions of Devices in DVP-PM 3.10 Special Auxiliary Relays [M], Special Data Register [D] The types and functions of special auxiliary relays (special M) are listed in the table below. Special M and special D marked with “*” will be further illustrated in 3.11. Columns marked with “R” refers to “read only”, “R/W” refers to “read and write”, “-“ refers to the status remains unchanged and “#” refers to that system will set it up according to the status of the PLC.. DVP-PM Application Manual 3-18 OFF MANU AUTO Special Page Function 10M 20D 20M Ø Ø Ø Attrib. Latched Default M number ON AUTO MANU M1000* Monitoring normally open contact::
ON when AUTO is activated ○ ○ ○ OFF ON OFF R NO OFF 3-35 M1001* Monitoring normally closed contact: OFF when AUTO is activated ○ ○ ○ ON OFF ON R NO ON 3-35 M1002* Enable single positive pulse at the moment when AUTO is activated (Normally OFF). Pulse width = scan time. ○ ○ ○ OFF ON OFF R NO OFF 3-35 M1003* Enable single negative pulse at the moment when AUTO is activated (Normally ON). Pulse width = scan time. ○ ○ ○ ON OFF ON R NO ON 3-35 M1008 Watchdog timer (ON: PLC WDT time out) ○ ○ ○ OFF OFF - R NO OFF - M1009 Indicate that LV status occurred.
○ ○ ○ OFF - - R NO OFF M1011 10ms clock pulse, 5ms ON / 5ms OFF ○ ○ ○ OFF - - R NO OFF - M1012 100ms clock pulse, 50ms ON / 50ms OFF ○ ○ ○ OFF - - R NO OFF - M1013 1s clock pulse, 0.5s ON / 0.5s OFF ○ ○ ○ OFF - - R NO OFF - M1014 1min clock pulse, 30s ON / 30s OFF ○ ○ ○ OFF - - R NO OFF - M1025 Indicate incorrect request for communication (When PC or HMI is connected with DVP-PM, and DVP-PM receives illegal request for communication service during the data transmission, M1025 will be set, and the error code will be stored in D1025.) ○ ○ ○ OFF OFF - R NO OFF - M1026 RAMP mode selection ○ ○ ○ OFF - - R/W NO OFF M1029 CH0 (Y0, Y1) pulse output execution completed.
○ ○ ○ OFF - - R NO OFF M1031 Clear all non-latched memory ○ ○ ○ OFF - - R/W NO OFF - M1032 Clear all latched memory ○ ○ ○ OFF - - R/W NO OFF - M1033 Memory latched when not in operation ○ ○ ○ OFF - - R/W NO OFF - M1034 Disable all Y outputs ○ ○ ○ OFF - - R/W NO OFF - M1035 Enable STOP0/START0 as external input points ○ ○ ○ OFF OFF OFF R/W NO OFF - M1036* Enable continouous interpolation on application instructions ○ ○ ○ OFF OFF OFF R/W NO OFF 3-46 M1039* Fix scan time ○ ○ ○ OFF - - R/W NO OFF 3-39 M1048 Indicating alarm status ○ ○ ○ OFF - - R NO OFF - M1049 Enabling alarm monitoring ○ ○ ○ OFF - - R/W NO OFF - M1072 PLC status (AUTO / MANU), ON = AUTO (communication) ○ ○ ○ OFF ON OFF R/W NO OFF - M1074* Enable OX motion subroutine ╳ ○ ○ OFF - - R/W NO OFF 3-39 M1077 Battery in low voltage, malfunction or no battery ○ ○ ○ OFF - - R/W NO OFF - M1087 Indicate current LV status ○ ○ ○ OFF - - R/W NO OFF -