3 Functions of Devices in DVP-PM 3.11 Functions of Special Auxiliary Relays and Special Registers Function Group: DVP-PM Operation Flag Number: M1000 ~ M1003 Explanations: 1. M1000: NO contact for monitoring DVP-PM status. M1000 remains “ON” when DVP-PM is running. M1000 Y0 DVP-PM is running Remains ON in DVP-PM AUTO status Remains ON 2. M1001: NC contact for monitoring PLC status. M1001 remains “OFF” when PLC is running. 3. M1002: Enables single positive pulse for the first scan when DVP-PM AUTO is activated. Remains OFF after the initial pulse. Used to initialize registers, ouptuts, or counters when AUTO is executed. Pulse width = one scan time 4. M1003:
Enables single negative pulse for the first scan when DVP-PM AUTO is activated. Remains ON after the initial pulse. Used to initialize registers, ouptuts, or counters when AUTO is executed. Pulse width = one scan time DVP-PM RUN M1000 M1001 M1002 M1003 Scan time Function Group: Monitor Timer Number: D1000 Explanations: 1. Monitor timer is used for moitoring PLC scan time. When the scan time exceeds the set value (SV) in the monitor timer, the red ERROR LED will be ON and all outputs will be “OFF”. 2. The default in the monitor timer is 200ms. If the program is long or the operation is too complicated, MOV instruction can be used to modify SV. See the example below for setting SV as 300ms.
M1002 0 Initial pulse 3. The maximum SV in the monitor timer is 32,767ms. However, care should be taken when adjusting SV. If SV in D1000 is too big, it cost much longer to detect operation errors. Therefore, SV is suggested to be shorter than 200ms. DVP-PM Application Manual 3-35 MOV K300 D1000