AS Series Operation Manual AS-F2DA Two DC analog signal output channels: _2 *1: The conversion time is the time for each channel to convert signals to hardware input signals. If you need to calculate a complete conversion time, you need to add the PLC scan time. *2: Use the MOV instruction to move the value to the SR to obtain the corresponding voltage output value. AS-F232 The AS series PLC is built with COM1 (RS-485), and COM2 (RS-485). You can use this extension card for communication with different interfaces such as RS-232 and a PC. The Communication functions are the extension card, go to the HWCONFIG in the ISPSoft for communication setup. same as the built-in ones.
You can set the communication port as a slave or a master node. After installing the Wiring example AS-F232 (DB9 female) + + Superior machine DB9 male to DB9 female (standard cable) 2-77 Item Voltage Output Current Output Analog Signal 0 V - 10 V 4 mA - 20 mA Resolution 12-bit 12-bit Digital Conversion Limit 0 - 4000 0 - 4000 Error Rate room temperature: ±0.5% ; full temperature range: ±1.0% Impedance Allowance ≥1 kΩ ≤500 Ω Conversion Time*1 2ms / CH Characteristic Curve 10V Output Voltage 0 4000 Digital Value Input 20mA Output Current 4 4000 Digital Value Input Digital Value Output*2 Card 1 SR172 (CH1) SR173 (CH2) Card 2 SR174 (CH1) SR175 (CH2)