Chapter 2 Specifications and System Configuratio n AS-FCOPM With its own standalone communication port, the extension card can work independently and can be set as a slave or a master node. After installing the extension card, go to the HWCONFIG in ISPSoft to set up the communication. Wiring example 2_ Master node Slave node Slave node Terminal resistor (120 ohm) AS-F422 You can use this extension card for communication with Delta HMI series or other devices through the RS-422 communication port. The Communication functions are the same as the built-in ones. You can set the communication port as a slave or a master node.
After installing the extension card, go to the HWCONFIG in ISPSoft to set up communication. Wiring example of the communication with Delta HMI DOPA series via COM2 AS-F422 Delta HMI series DOPA COM2/DB-9 AS-F485 With its own standalone communication port, the extension card can work independently and can be set as a slave or a master node. After installing the extension card, go to the HWCONFIG in ISPSoft to set up communication.
Wiring example Master node Slave node Slave node SG Terminal resistor (120 ohm) Terminal resistor (120 ohm) Shielded cable 2-78 CAN H _ CAN L _ CAN H _ CAN L _ nal tor ohm) Te re (1 Shielded cable AN H _ CAN L _ R 1 R 2 3 T 4 T + Tx+ 3 6 RT 4 7 RT 2 8 1 9 CT CT S- - Tx- S+ S+ + Rx+ - Rx- S- D+ D- D+ D- SG SG D + D- Shielded cable