Chapter 8 Hardware Configuration You can identify a device by means of device name. When several devices are connected on a network, you can check whether a device connected to the computer is the device you expect with the device name. If you want to download or upload the program, but the name of the CPU module is different from the name attached to the model in the project management area, the system reminds you to check the name of the CPU module and the name attached to the model in the project management area. System Parameter On the System Parameter page, you can set parameters by entering appropriate values or by selecting from a list.
Clear Non-latched area when Stop Run This determines whether the states and values of the non-latched devices are cleared when the PLC changes from Stop to Run. Disable: all the states and values in the non-latched devices stay the same. Enable: all the states and values in the non-latched devices are cleared and restored to defaults. Y keeps outputting when RUN Stop This determines the states of the Y devices when the CPU module begins to run or stop. Off: all Y devices are set to OFF. Retain: the states of the Y devices stay the same.
I/O module CONFIG by Auto/Manual when Power On This determines whether the CPU module is automatically configured, or you configure the parameters in HWCONFIG. Auto: the CPU module is automatically configured. Manual: you configure the parameters in HWCONFIG and PLC checks the parameters automatically once it is supplied with power. Manual + Flags: This function is available for PLC with firmware V1.06.00 or above and you need to use ISPSoft V3.07 or above to execute this function. The selection “Manual + Flags” is for the setting option “I/O module allocation setting when Power ON” in ISPSoft.
Select this option, you need to use it with flags _8 SM230-SM261 (refer to Section 2.2.7 in AS Series Programming Manual for more details). For less module applications, you can simply use special flags to mark which I/O module will NOT be used to meet the actual I/O module placement. In this mode, you can use the same PLC program and download the I/O allocation table once for various I/O applications. 8-19