AS Series Operation Manual Example: Step 1: Select “Manual + Flags” for the setting option “I/O module allocation setting when Power ON” in HWCONFIG Step 2: Plan an entire module allocation and download the I/O allocation table to HWCONFIG Step 3: When 08AD and 04TC are not needed in the application, you can set the flags SM236 (indicating 08AD) and SM239 (indicating 04TC) to OFF to meet the actual I/O module placement. Actual I/O module placement Select Action when I/O Module parameter with manual CONFIG Different _8 This determines which action is taken when the actual settings are not the same as the parameters that you manually set when the previous setting option is set to Manual .
Auto update: the CPU module is automatically configured. Show error: the CPU module shows an error. CPU module Stop when I/O Module No Response This determines how the CPU module and other modules react when a connected extension module is not responding. Stop: the CPU module stops running and sends an error. Keep Run: the CPU module and I/O modules keep running. 8-20