Delta Electronics — 8.2.2.7 Options - Function Card 2 Setting

Chapter 8 Hardware Configuration 8.3 Data Exchange 8.2.2.7 Options - Function Card 2 Setting In the Device Settings dialog box, after you click the Data Exchange-COM1, Data Exchange-COM2 or Data Exchange- Ethernet tab, you can set the parameters for the data exchange table for the communication port built into the AS Series module. The AS Series module can be a master and exchange data with remote slave devices through COM1 and COM2 using the Modbus protocol, or through an Ethernet port using the Modbus TCP protocol.  There are three ways to start the data exchange: Program Control, PLC Run and Always Enable. Program Control (default):

The program in the PLC determines whether to perform the set data exchange. You can set SM flags to start the data exchange. Refer to Section 2 .2.7 for more information on Special Auxiliary Relays (SM). This mode is useful for applications that the time for CPU to power-on and power-off is not certain. PLC Run means that the set data exchange is performed automatically when PLC switches from STOP to RUN state. This mode is useful for applications that the Slave is ahead of time to communicate before the CPU module is ready. Always Enable means that the data exchange is performed constantly when the PLC is powered on (whether PLC _8 is in the RUN state or not).

This mode is useful for applications that the Slave is always ready to communicate. These are three ways to start the data exchange. If you need to stop any communication, you can set its specific SM to OFF to stop the communication.  Add a new row in the data exchange table in area  by clicking Add . Move the selected data exchange row up or down by clicking Move Up and Move Down . Delete the selected data exchange row by clicking Delete . Copy the selected data exchange row by clicking Copy. You can then paste it back into the table as the last row.  The following table explains the columns in the data exchange table. 8-45