Delta Electronics — 8.3.1.1 Data Exchange - COM1 and Data Exchange - COM2

AS Series Operation Manual 8.3.1.1 Data Exchange - COM1 and Data Exchange - COM2 On the Data Exchange-COM1 or Data Exchange-COM2 tab , double-click row in the data exchange table to set to open the Item dialog box as shown below. Select the Enable check box to enable the data exchange table in the mode mentioned above. Remote Address is the address of the target slave for data exchange. The Shortest Update Cycle is the period for data exchange of the data exchange table. The connection times out if the target device does not make any response within the time specified by Connection Timeout .

Select Support Read/write synchronization (Function code 0x17) to have the master complete reading and writing in a single command to improve the efficiency of data exchange. This uses the specific Modbus function code. Make sure that all devices in data exchange support the Modbus function code for read and write synchronization. Otherwise, _8 the attempt to read and write fails due to the failure to identify function codes after receiving the command from the master device. Remote Device Type is the model of a target slave including the Delta PLC and standard Modbus devices.

8-46 Name Description Item The number of the block for data exchange Enable Selects whether to enable the data exchange table when the data exchange is performed. Station Address/ IP Address The slave station address for the data exchange table. You can set one address for multiple data exchange tables. It is a station address under the COM1 and COM2 tabs, and IP under the Ethernet tab. Local Address The device address range used by the master in the data exchange table > 「 >」: Output: the data block where the master writes to a slave Remote Address This is the device address range used by a slave in the data exchange table.

The device range is in hexadecimal if the slave in the data exchange table is a user- defined Modbus Device. Quantity This is the size of the data exchange table, which is consistent with the result calculated from the device range.