Chapter 9 Ethernet Specification and Operation 9.6 Troubleshooting This section provides an overview of error codes and troubleshooting for the AS Series. 9.6.1 Error Code Classification There are two types of error code categories for the AS Series: Configuration Errors, and Application Errors. These error codes are defined by the ODVA for EtherNet/IP errors. Refer to the following table for AS Series error codes.
9.6.2 Error Codes & How to fix them 9.6.2.1 Configuration Errors (EIP Builder only shows Low word error codes) 9_ 9-47 Error Code Classification Description 1st Phase 2nd Phase Category Item Configuration error EDS files mismatched Mismatched EDS files lead to I/O connection failure. * Data exchange setup error Data exchange setup error lead to I/O connection failure. * Application error Ethernet/IP error EtherNet/IP communication failure * * Only the last 2 bytes of the error code are shown; for example, only 011C appears for the error code H’1101011C.
Category Error Code Description How to fix them EDS Files Mismatched H’1101011C The Transport Class field values of the Transport Class and Trigger in the EDS file are mismatched. 1. Check if the product information and the EDS file match. 2. Reload the EDS file. 3. Ask the vendor of the device for the EDS file. H’11010114 The Vender ID or the Product Code in the EDS file is mismatched. 1. Check if the product information and the EDS file match. 2. Reload the EDS file. 3. Ask the vendor of the device for the EDS file. H’11010115 The device type parameters in the EDS file are mismatched. 1. Check if the product information and the EDS file match. 2. Reload the EDS file. 3.
Ask the vendor of the device for the EDS file. H’11010116 The revision parameters in the EDS file are mismatched. 1. Check if the product information and the EDS file match.