Delta Electronics — 10.4.1 Data Structure of SDO Request Message

Chapter 10 CANopen Function and Operation The following table shows the data format of the SDO response message.  Status code: The following table lists the status code values in the response message.  ResID: the same as the request ID in the request message.  Size: the length of the message data, maximum of 20 bytes. The unit is bytes. When writing, the maximum is four; the data length is decided by the data type of index and subindex when reading.  Node ID: the node address of the target equipment on CANopen network.  Type:

in the SDO response message, 43 (Hex) refers to reading four bytes of data; 4B (Hex) refers to reading two bytes of data; 4F (Hex) refers to reading one byte of data; 60 (Hex) refers to writing 1/2/4 byte(s) of data; 80 (Hex) refers to stopping SDO command. 10 10-21 Response message PLC device High byte Low byte D24000 Message Header ResID Status code D24001 Reserved Size D24002 Type Node ID D24003 Message Data High byte of main index Low byte of main index D24004 Reserved Sub-index D24005 Datum 1 Datum 0 D24006 Datum 3 Datum 2 D24007~D24031 Reserved Status code Explanation 0 No data transmission request 1 SDO message transmission succeeds. 2 SDO message is being transmitted. 3 Error:

SDO transmission time-out 4 Error: Illegal command code 5 Error: the length of the transmitted data is illegal. 6 Error: the length of the response data is illegal. 7 Error: Equipment to be sent messages is busy. 8 Error: Illegal type 9 Error: Incorrect node address 0A Error message (See the error code for SDO response message) 0B-FF Reserved