Delta Electronics — 10.4.1 Data Structure of SDO Request Message

AS Series Operation Manual Example 1: write 010203E8 (hex) to (Index_subindex) 212D_0 in slave of No. 3 through SDO; the data type of (Index_subindex) 212D_0 is double words (32 bits).  Request data:  Response data: Example 2: read the value of (Index_subindex) 212D_0 in slave of No. 3 through SDO; the data type of (Index_subindex) 212D_0 is double words (32 bits).  Request data:

_10 10-22 Request message PLC device High byte(Hex) Low byte(Hex) D25000 Message Header ReqID=01 Command =01 D25001 Reserved =0 Size =8 D25002 Type =02 Node ID =03 D25003 Message data Main index high byte =21 Main index low byte =2D D25004 Reserved =0 Subindex =0 D25005 Datum 1=03 Datum 0=E8 D25006 Datum 3=01 Datum 2=02 Response message PLC device High byte(Hex) Low byte(Hex) D24000 Message Header ResID =01 Command =01 D24001 Reserved =0 Size =4 D24002 Type =60 Node ID =03 D24003 Message data Main index high byte =21 Main index low byte =2D D24004 Reserved =0 Subindex =0 D24005 Datum 1=00 Datum 0=00 D24006 Datum 3=00 Datum 2=00 Request message PLC device High byte(Hex) Low byte(Hex) D25000 Message Header ReqID =01 Command =01 D25001 Reserved =0 Size =4 D25002 Type =01 Node ID =03 D25003 Message data Main index high byte =21 Main index low byte =2D D25004 Reserved =0 Subindex =0 D25005 Datum 1=0 Datum 0=0 D25006 Datum 3=0 Datum 2=0