Delta Electronics — 12.1.4 Viewing System Log and Error Step

AS Series Operation Manual  Error Code: Error codes in the error log.  Date & Time: The date and time the error occurred. The most recently occurring error is listed on the top.  The last column shows the descriptions for the error. (3) If the error occured is an exceeding device ragne error (SM0 = ON) or a program syntax error (SM5 = ON), you can use the following steps to see the problematic step in the program.  SM0 = ON: Check the value (32-bit) in SR1 to see the latest exceeding device range error in the program. _12  SM5 = ON: Check the value (32-bit) in SR5 to see the latest syntax error step in the program.

 After knowing which the problematic step is, go to ISPSoft -> Edit -> Step positioning and then enter the number of the problematic step, the system will take you to the specified step in the program. 12-6