Delta Electronics — 12.2.2 ERROR LED Indicators Blinking Every 0.5 Seconds

Chapter 12 Troubleshooting 12.2 Troubleshooting for CPU Modules Check the LED indicators and the error codes from the CPU module and refer to the following table for troubleshooting. V in the Log column indicates the error is recorded in the log. X in the Log column indicates the error is not recorded in the log. H in the Log column indicates whether or not you can set recording the error in the log in HWCONFIG. 12.2.1 ERROR LED Indicators Are ON 12_ 12.2.2 ERROR LED Indicators Blinking Every 0.5 Seconds 12-7 Error Code Description Solution Flag Log (16#) 000A Scan timeout 1. Check the setting of the watchdog timer in HWCONFIG. 2.

Check whether the program causes a long scan time SM8 V Error Code Description Solution Flag Log (16#) 000C The program in the PLC is damaged. Download the program again. SM9 V 0010 CPU memory is denied. If the problem persists, contact the local authorized distributors. SM9 V 002E CPU external memory access is denied. If the problem persists, contact the local authorized distributors. SM9 V 002F PLC programs are not consistent with the system logs. Download the program again. SM34 V 0070 The arrangement of the function cards is not consistent with the settings. Check whether the settings in HWCONFIG are consistent with the arrangement of the function cards.

SM10 V 0102 The interrupt number exceeds the range. Check the syntax error step in the program. Modify and compile the program and then download the program again. SM5 X 0202 The MC instruction exceeds the range. SM5 X 0302 The MCR instruction exceeds the range. SM5 X 0D03 The operands used in DHSCS are not used properly. SM5 X 0E05 The operands HCXXX used in DCNT are not used properly. SM5 X 1300 - 130F Errors occurred in the remote modules Refer to Section 12.3.4 for more information on the error codes for the remote modules. SM30 V 1402 The arrangement of the I/O modules is not consistent with the settings.

Check whether the settings in HWCONFIG are consistent with the arrangement of the I/O modules. SM10 V 140B More than four communication modules. Check the total number of communication modules (maximum is four). SM10 V