Chapter 12 Troubleshooting 12.2 Troubleshooting for CPU Modules Check the LED indicators and the error codes from the CPU module and refer to the following table for troubleshooting. V in the Log column indicates the error is recorded in the log. X in the Log column indicates the error is not recorded in the log. H in the Log column indicates whether or not you can set recording the error in the log in HWCONFIG. 12.2.1 ERROR LED Indicators Are ON 12_ 12.2.2 ERROR LED Indicators Blinking Every 0.5 Seconds 12-7 Error Code Description Solution Flag Log (16#) 000A Scan timeout 1. Check the setting of the watchdog timer in HWCONFIG. 2.
Check whether the program causes a long scan time SM8 V Error Code Description Solution Flag Log (16#) 000C The program in the PLC is damaged. Download the program again. SM9 V 0010 CPU memory is denied. If the problem persists, contact the local authorized distributors. SM9 V 002E CPU external memory access is denied. If the problem persists, contact the local authorized distributors. SM9 V 002F PLC programs are not consistent with the system logs. Download the program again. SM34 V 0070 The arrangement of the function cards is not consistent with the settings. Check whether the settings in HWCONFIG are consistent with the arrangement of the function cards.
SM10 V 0102 The interrupt number exceeds the range. Check the syntax error step in the program. Modify and compile the program and then download the program again. SM5 X 0202 The MC instruction exceeds the range. SM5 X 0302 The MCR instruction exceeds the range. SM5 X 0D03 The operands used in DHSCS are not used properly. SM5 X 0E05 The operands HCXXX used in DCNT are not used properly. SM5 X 1300 - 130F Errors occurred in the remote modules Refer to Section 12.3.4 for more information on the error codes for the remote modules. SM30 V 1402 The arrangement of the I/O modules is not consistent with the settings.
Check whether the settings in HWCONFIG are consistent with the arrangement of the I/O modules. SM10 V 140B More than four communication modules. Check the total number of communication modules (maximum is four). SM10 V