AS Series Operation Manual _12 12-8 Error Code Description Solution Flag Log (16#) 140D More than 32 extension modules. Check the total number of extension modules (maximum is 32). SM10 V 140E More than eight remote modules on the right side of the CPU module. Check the total number of remote modules on the right side of the CPU module (maximum is 8). SM30 V 1600 The extension module ID exceeds the range. 1. Make sure the module is properly connected to the CPU module and turn the modules on again. 2. If the problem persists, contact the local authorized distributors. SM10 V 1601 The extension module ID cannot be set. 1.
Make sure the module is properly connected to the CPU module and turn the modules on again. 2. If the problem persists, contact the local authorized distributors. SM10 V 1602 The extension module ID is duplicated. 1. Make sure the module is properly connected to the CPU module and turn the modules on again. 2. If the problem persists, contact the local authorized distributors. SM10 V 1603 The extension module cannot be operated. 1. Make sure the module is properly connected to the CPU module and turn the modules on again. 2. If the problem persists, contact the local authorized distributors. SM10 V 1604 Extension module communication timeout 1.
Make sure the module is properly connected to the CPU module and turn the modules on again. 2. If the problem persists, contact the local authorized distributors. SM10 V 1605 Hardware failure If the problem persists, contact the local authorized distributors. SM10 V 1606 Errors on the communication module function card Make sure the function card is properly connected to the CPU module and turn the modules on again. SM10 V 1607 The external voltage is abnormal. Check whether the external 24 V power supply to the module is normal. SM10 V 1608 The Internal factory calibration or the CJC is abnormal. If the problem persists, contact the local authorized distributors.
SM10 V 1609 - 160F Reserved (Error codes for the extension modules) 200A Invalid instruction Check the syntax error step in the program. Modify and compile the program and then download the program again. SM5 V 6010 The number of MODBUS TCP connections exceeds the range. Check the number of superior devices (maximum is 32). SM 1092 V 6011 The number of EtherNet/IP connections exceeds the range. Check the number of connections (maximum is 16). SM 1093 V C000 - CFFF The program syntax is incorrect. Save the PLC program and hand the file to the company or the technicians.