Delta Electronics — 12.2.6 BAT. LOW LED Indicators Blinking Every 0.5 Seconds

Chapter 12 Troubleshooting 12.2.3 ERROR LED Indicators Blinking Rapidly Every 0.2 Seconds The blinking happens when the power supply 24 VDC of the CPU module is disconnected, or the power supply is not sufficient, not stable or abnormal. 12_ 12.2.4 ERROR LED Indicators Slow Blinking Every 3 Seconds and Lighting up for 1 Second 12.2.5 BAT. LOW LED Indicators Are ON The blinking happens when there is no battery (CR1620) or the power is low. Turn this option off in the HWCONFIG > current time (default is enabled). CPU > Device Setting > Show Battery Low Voltage Error CPU when you don’t need the RTC function to keep track of the 12.2.6 BAT.

LOW LED Indicators Blinking Every 0.5 Seconds The blinking happens when RTC cannot keep track of the current time. 12-9 Error Code Description Solution Flag Log (16#) 002A The external voltage is abnormal. Check whether the external 24 V power supply to the module is normal. SM7 V Error Code Description Solution Flag Log (16#) 1500 Connection lost in the remote modules Check the network connection cable. SM30 V 1502 - 150F Errors occurred in the remote modules Refer to Section 12.3.4 for more information on the remote module error codes. SM30 V 1800 - 180F Errors occurred in the extension modules Refer to Section 12.3 for more information on the extension module error codes.

SM10 V 1900 - 191C Heartbeat errors occurred in the slave for the Delta ASD-A2 control. 1. Check the CANopen connection cable. 2. Check if the specific slave is working properly. Note: The last 2 digits of the error code represent the ID number of the slave (convert hexadecimal to decimal). - V Error Code Description Solution Flag Log (16#) 0027 Battery Low Change battery or turn this option off SM219 X Error Code Description Solution Flag Log (16#) RTC cannot keep track of the If the problem persists, contact the local authorized 0026 SM218 V current time distributors.