Delta Electronics — 12.2.9 Other Errors (Without LED Indicators)

AS Series Operation Manual 12.2.7 The LED RUN and ERROR Indicators are Blinking Simultaneously Every 0.5 Seconds supplied to the CPU module, it means errors occurred during the previous firmware upgrade. Users need to upgrade the The blinking happens when the firmware of the CPU module is being upgraded. If this happens once the power is firmware again or contact your point of purchase. 12.2.8 The RUN and LED Indicators are Blinking One After Another Every 0.5 Seconds. _12 The blinking happens when the CPU module memory card is backing up, restoring, or saving.

If you are using AS218 Series CPU and without engaging any SD card, the RUN and LED indicators blinking indicates the AIO firmware is being updated. If the blinking happens at the instant when the CPU is supplied with power, the blinking means AIO firmware update failed and you need to update the firmware again. If you are not updating the AIO firmware, the blinking indicates CPU error and you need to contact the local authorized distributors. 12.2.9 Other Errors (Without LED Indicators) 12-10 Error Code Description Solution Flag Log (16#) 0011 The PLC ID is incorrect. Check the PLC ID. SM34 V 0012 The PLC password is incorrect. Check the PLC password.

SM34 V 002D The PLC maximum password attempts exceeded. Reset the CPU module or restore the CPU module to its default settings. SM34 V 0050 The memories in the latched special auxiliary relays are abnormal. 1. Reset the CPU module or restore the CPU module to its default settings, and then download the program and the parameters again. 2. If the problem persists, contact the local authorized distributors. SM6 V 0051 The latched special data registers are abnormal. 1. Reset the CPU module or restore the CPU module to its default settings, and then download the program and the parameters again. 2. If the problem persists, contact the local authorized distributors.

SM6 V 0052 The memories in the latched auxiliary relays are abnormal. 1. Reset the CPU module or restore the CPU module to its default settings, and then download the program and the parameters again. 2. If the problem persists, contact the local authorized distributors. SM6 V 0054 The latched counters are abnormal. 1. Reset the CPU module or restore the CPU module to its default settings, and then download the program and the parameters again. 2. If the problem persists, contact the local authorized distributors. SM6 V 0055 The latched 32-bit counters are abnormal. 1.

Reset the CPU module or restore the CPU module to its default settings, and then download the program and the parameters again. 2. If the problem persists, contact the local authorized distributors. SM6 V