Chapter 12 Troubleshooting 12_ 12-11 0056 The latched special auxiliary relay is abnormal. 1. Reset the CPU module or restore the CPU module to its default settings, and then download the program and the parameters again. 2. If the problem persists, contact the local authorized distributors. SM6 V 0059 The latched data registers are abnormal. 1. Reset the CPU module or restore the CPU module to its default settings, and then download the program and the parameters again. 2. If the problem persists, contact the local authorized distributors. SM6 V 005D The CPU module does not detect a memory card. Check that the memory card is inserted correctly into the CPU module.
SM453 V 005E The memory card is initialized incorrectly. Check whether the memory card is broken. SM453 V 0063 An error occurs when data is written to the memory card. Check whether the file path is correct or whether the memory card is malfunctioning. SM453 V 0064 A file in the memory card cannot be read. Check whether the file path is correct, or whether the file is damaged. SM453 V 1950 The initialization of the Delta ASD-A2 control has not yet been completed, the CANopen instructions cannot be executed. 1. Check the CANopen connection cable. 2. Check if the specific slave is working properly. 3. If nothing is wrong, initialize the Delta ASD-A2 again.
- V 19B0 Heartbeat timeout occurred in the slave mode Check the CANopen connection cable. - V 19B1 The data length of PDO (process data object) in the slave mode is not matched with the setting. Revise the PDO data length setting in the slave mode and download the setting again. - V 19E1 The data length of PDO (process data object) in the slave mode is not matched with the setting of the scan list. Refer to CANopen communication related descriptions in AS Series Operation Manual for more details on the error codes 19E1 to 19E8. Revise the PDO data length setting in the slave mode and download the setting again. - V 19E2 PDO in the slave mode is not received.
Check if the configurations are correctly set. - V 19E3 The function of auto downloading SDO fails at the first startup. Check if the SDO contents for auto downloading are correct. - V 19E4 PDO configurations are set incorrectly. Make sure to set the PDO configurations correctly. - V 19E5 The main settings are not consistent with the connected slave. Check ifthe main settings are consistent with the connected slave. - V 19E6 This slave does NOT exist in this network. Make sure power of the slave is working properly and the network cable is well-connected.
- V 19E7 Control timeout occurred in the slave mode Make sure power of the slave is working properly and the network cable is well-connected. - V 19E8 The master ID is duplicated. Revise IDs for mater and slave. Make sure no duplications. - V 19F3 Incorrect configuration table 1. Download the configuration table again. 2. If the problem persists, contact the local authorized distributors. - V