Delta Electronics — 12.3.1.2 ERROR LED Indicators Blinking Every 0.2 Seconds

AS Series Operation Manual 12.3 Troubleshooting for I/O Modules  Introduction to troubleshotting modules Digital I/O, analog I/O, temperature measurement, positioning, counter, load cell, and network modules can be installed in an AS Series system. There are 2 types of error codes; error and warning. The CPU module and its modules stop operating when errors occur. The CPU modules and its modules do not stop operating when warnings are triggered. _12 12.3.1 Troubleshooting for Analog Modules (AD/DA/XA) and Temperature Modules (RTD/TC) 12.3.1.1 ERROR LED Indicators Are ON You can set up HWCONFIG to have the following errors appear as warnings when they occur.

Otherwise, when an error occurs, only an error message appears. 12.3.1.2 ERROR LED Indicators Blinking Every 0.2 Seconds The following errors are specified as warnings to ensure that the CPU module can still run even when the warnings are triggered by its AIO modules. The following first 4 error codes are set as warnings by default in HWCONFIG; CPU must STOP running immediately when the first 4 errors occur. 12-18 Error Description Solution Code 16#1605 Hardware failure If the problem persists, contact the local authorized distributors. 16#1607 The external voltage is abnormal. Check the power supply. 16#1608 The factory calibration or the CJC is abnormal.

If the problem persists, contact the local authorized distributors. Error Description Solution Code 16#1801 The external voltage is abnormal. Check the power supply. 16#1802 Hardware failure If the problem persists, contact the local authorized distributors. 16#1804 The factory calibration is abnormal. If the problem persists, contact the local authorized distributors. 16#1807 The CJC is abnormal. If the problem persists, contact the local authorized distributors. 16#1808 The signal received by channel 1 exceeds the range of analog inputs (temperature). Check the signal received by channel 1 16#1809 The signal received by channel 2 exceeds the range of analog inputs (temperature).

Check the signal received by channel 2 16#180A The signal received by channel 3 exceeds the range of analog inputs (temperature). Check the signal received by channel 3 16#180B The signal received by channel 4 exceeds the range of analog inputs (temperature). Check the signal received by channel 4