Delta Electronics — 12.3.3.1 ERROR LED Indicators Are ON

Chapter 12 Troubleshooting 12_ 12.3.2 Troubleshooting for the Positioning Module AS02/04PU 12.3.2.1 ERROR LED Indicators Blinking Every 0.2 Seconds 12.3.3 Troubleshooting for the High-Speed Counter Module AS02HC 12.3.3.1 ERROR LED Indicators Are ON 12-19 Error Description Solution Code 16#180C The signal received by channel 5 exceeds the range of analog inputs (temperature). Check the signal received by channel 5 16#180D The signal received by channel 6 exceeds the range of analog inputs (temperature). Check the signal received by channel 6 16#180E The signal received by channel 7 exceeds the range of analog inputs (temperature).

Check the signal received by channel 7 16#180F The signal received by channel 8 exceeds the range of analog inputs (temperature). Check the signal received by channel 8 - When power-on, the module is not detected by CPU module. Check if the connection between module and CPU module is working. If not, connect again. Error Description Solution Code 16#1802 Hardware failure If the problem persists, contact the local authorized distributors. Error Description Solution Code 16#1605 Counted result in the latched area is not retainable (major error) Counted data is lost. Switch the module power OFF and ON again. The error code is cleared by the system.

If the problem persists, contact the local authorized distributors. 16#1606 Module settings in the latced area is not retainable. (major error) Module setting data is lost. Switch the module power OFF and ON again. Download the HWCONFIG settings again to clear the error code. If the problem persists, contact the local authorized distributors. 16#1607 Module setting error (major error) Check if the setting in HWCONFIG is consistent with the actual placement. If the problem persists, contact the local authorized distributors.