AS Series Operation Manual 12.3.3.2 ERROR LED Indicators Blinking Every 0.5 Seconds The following errors are specified as warnings to ensure that the CPU module can still run even when the warnings are triggered by its AIO modules. _12 12.3.4 Troubleshooting for the Load Cell Module AS02LC 12.3.4.1 ERROR LED Indicators Are ON You can set up HWCONFIG to have the following errors appear as warnings when they occur. Otherwise, when an error occurs, only an error message appears. 12-20 Error Description Solution Code 16#1800 Counter overflow / underflow on CH1 Check the counter result. If the alarm is not required, disable the alarm output function in HWCONFIG.
Use any of the followings to clear the error code: clear, reset, preset the counter, restart the module, or execute DHCCNT instruction again. 16#1801 Counter overflow / underflow on CH2 16#1802 Linear count exceeding the set upper/lower limit on CH1 Check the signal received by channel 1 and 2. Hardware counter is still counting; when the number is accumulated to the maximum and go back to the minimum, the error code will be cleared.
16#1803 Linear count exceeding the set upper/lower limit on CH2 16#1804 The variation in relation to a SSI encoder position exceeding the limit on CH1 Check if there is any interruption and check the device specification to see if the offset setting is matching with the actual placement. When the next reading is normal, the error code will be cleared. 16#1805 The variation in relation to a SSI encoder position exceeding the limit on CH2 16#1806 Abnormal SSI communication on CH1 Check the execution of DHCCNT instruction. If it is parity check, check is there is any interruption and check if the data format is correct.
Check if the device wiring is secure, and if the encoder power supply is normal. 16#1807 Abnormal SSI communication on CH2 16#1808 SSI absolute position cross zero point on CH1 Check the SSI absolute encoder specification and modify the setting accordingly. If the alarm is not required, disable the alarm output function in HWCONFIG. Use any of the followings to clear the error code: clear, reset, preset the counter, restart the module, or execute DHCCNT instruction again. 16#1809 SSI absolute position cross zero point on CH2 Error Description Solution Code 16#1605 Hardware failure (that is, the driver board) If the problem persists, contact the local authorized distributors.
16#1607 The external voltage is abnormal. Check the power supply.