Chapter 12 Troubleshooting 12.3.4.2 ERROR LED Indicators Blinking Every 0.2 Seconds The following errors are specified as warnings to ensure that the CPU module can still run even when the warnings are triggered by its AIO modules. The following first 3 error codes are set as warnings by default in HWCONFIG; CPU must STOP running immediately when the first 3 errors occur. 12_ 12.3.5 Troubleshooting for the Module AS04SIL IO-Link as a Communication Module 12.3.5.1 ERROR LED Indicators (Module Status) Blinking Every 0.2 Seconds The following error codes identify possible errors when the AS04SIL module is installed on the right side of the CPU module or RTU and acts as a communication module.
12-21 Error Description Solution Code 16#1801 The external voltage is abnormal. Check the power supply. 16#1802 Hardware failure If the problem persists, contact the local authorized distributors. 16#1807 Diver board failure If the problem persists, contact the local authorized distributors. 16#1808 The signal received by channel 1 exceeds the range of analog inputs or the SEN voltage is abnormal. Check the signal received by channel 1 and the cable connections. 16#1809 The signal received by channel 1 exceeds the weight limit. Check the value input to channel 1 and the maximum weight setting. 16#180A The factory calibration in channel 1 is incorrect.
Check the weight calibration in channel 1. 16#180B The signal received by channel 2 exceeds the range of analog inputs or the SEN voltage is abnormal. Check the signal received by channel 2 and the cable connections. 16#180C The signal received by channel 2 exceeds the weight limit. Check the value input to channel 2 and the maximum weight setting. 16#180D The factory calibration in channel 2 is incorrect. Check the weight calibration in channel 1. - When power-on, the module is not detected by CPU module. Check if the connection between module and CPU module is working. If not, connect again. Error Description Solution Code 16#1605 Hardware failure 1.
Check that the module is securely installed. 2. Install a new AS04SIL or if the problem persists, contact the local authorized distributors. 16#1606 24VDC power supply is not sufficient and then recovered from low-voltage for less than 10 ms. Check whether the 24 V power supply to the module is normal.