Delta Electronics — 12.3.5.2 ERROR LED Indicators (Network Status) Blinking Every 0.1 Seconds

AS Series Operation Manual 12.3.5.2 ERROR LED Indicators (Network Status) Blinking Every 0.1 Seconds module or RTU and acts as a communication module.

The following error codes identify possible errors when the AS04SIL module is installed on the right side of the CPU _12 IO-Link Event Code Table 12-22 Error Code Description Solution 16#1800 Error occurs in IO-Link Master See the following IO-Link Event Code table for more information 16#1801 Error occurs in IO-Link device See the following IO-Link Event Code table for more information 16#1802 No external power supply Check the external power supply 16#1803 Error in the download of IO-Link device mapping tables Redownload the configuration by the software 16#1804 Failure to switch the process data parameter set Check if the configurations of the actual connected device are the same as the ones in the software.

IO-Link Type Event Solution Source Event Warning Error Notifica - IO-Lin k r IO-Lin k e Codes tion Maste Devic 16#4000 V Device temperature over- load Lower load V 16#4210 V Device temperature over- run Clear source of heat V 16#5101 V Device fuse blown Change fuse V 16#5110 V Power supply voltage over-run Check tolerance V 16#5111 V Power supply voltage under-run Check tolerance V 16#6320 V Parameter error Check device specificaitons V 16#6321 V Parameter missing Check device specifications V 16#7710 V Device short circuit Check installation V 16#8C10 V Process variable range over-run Check process data V 16#8C20 V Measurement range over- run Check application V 16#8C30 V Process variable range under-run Check process data V 16#8CA0 V No connected IO-Link device Check installation V 16#8CA1 V The version of the IO-Link protocol is different from the one configured.

Use matching IODD file and configured again. V 16#8CA2 V Connected device is different from the one configured in the software Check configurations and installation V 16#8CA3 Reserved V 16#8CA4 V IO-Link device process cable short circuit Check installation V