AS Series Operation Manual 12.3.7.2 ERROR LED Indicators Blinking Every 0.5 Seconds Error codes: _12 12.3.7.3 ERROR LED Indicators Blinking Every 0.2 Seconds This happens when the 24 VDC power supply for the remote module is not sufficient. Check the power supply. If the power supply is normal, remove the extension module from the CPU module and then check if the SCM remote module is out of order. Error codes: 12.3.8 Troubleshooting for AS01DNET Modules 12.4 Error Codes and LED Indicators for CPU Modules Refer to sections 12.4.6 and 12.4.7 for more details. A. Columns a. Error code: If an error occurs in the system, an error code is generated. b. Description: The description of the error c.
CPU status: If the error occurs, the CPU stops running, keeps running, or shows the status you defined for the error. Stop: The CPU stops running when the error occurs. Continue: The CPU keeps running when the error occurs. d. LED indicator status: If the error occurs, the LED indicator is ON, OFF, or blinks. ERROR: System error 12-26 Error Description Solution Code 16#1500 Remote module communication timeout Make sure the module is properly connected to the CPU module and turn the modules on again. 16#1502 Incorrect parameters Check the parameter in HWCONFIG. Download the parameter again.
16#1503 Extension module communication timeout Make sure the module is properly connected to the CPU module and turn the modules on again. 16#1505 The actual placement of the extension module is not consistent with the configurations. Check if the setting in HWCONFIG is consistent with the actual placement. Error Description Solution Code 16#1303 24VDC power supply is not sufficient and then recovered from low-voltage for less than 10 ms. Check whether the 24 V power supply to the module is normal.