Delta Electronics — 12.4.1 Error Codes and LED Indicators for CPU Modules

Chapter 12 Troubleshooting  Descriptions 12_ 12.4.1 Error Codes and LED Indicators for CPU Modules Note: refer to Section 12.3 for the status descriptions of the Error LED indicators. 12-27 Module Type LED indicator Descriptions There are five types of error indicator states for of the CPU module errors, including LED indicator ON, OFF, blinking fast, blinking normally, and blinking slowly. When the LED indicator is ON, blinking fast/normally, clear the problems first in order to run the CPU module. When the LED indicator is blinking slowly, indicating a warning type of error codes, it does not require immediate action. Clear the problems when the module is powered off. Error type: ON:

A serious error occurs in the module. CPU Error LED Blinking fast (every 0.2 seconds): unstable power supply or hardware Failure. Blinking normally (every 0.5 second): system program errors or system cannot run. Warning type: Blinking slowly (every one second and off for three seconds): a warning is triggered, but the system can still run. OFF: a warning is triggered, but the system can still run. You can modify the rules of how a warning is triggered, or use the SM/SR to show the warnings. ERROR LED indicator status Error CPU Description code status Blinking Blinking Blinking ON OFF fast normally slowly 000A Scan timeout Stop V 000C The program in the PLC is damaged.

Stop V 0010 The access to the memory in the CPU is denied. Stop V 0011 The PLC ID is incorrect. Continue V 0012 The PLC password is incorrect. Continue V 0026 RTC cannot keep track of the current time (the battery LED is blinking.) Continue 0027 Battery low (the battery LED is ON.) Continue 002A 24VDC power supply is not sufficient and then is recovered from low-voltage for less than 10 ms. Continue V 002D The PLC maximum password attempts exceeded. Continue V 002E The access to the external memory of the CPU is denied. Stop V 002F PLC programs are not consistent with the system logs. Stop V 0050 The memories in the latched special auxiliary relays are abnormal.

Continue V 0051 The latched special data registers are abnormal. Continue V