Delta Electronics — 12.4.1 Error Codes and LED Indicators for CPU Modules

AS Series Operation Manual _12 12-28 ERROR LED indicator status Error CPU Description code status Blinking Blinking Blinking ON OFF fast normally slowly 0052 The memories in the latched auxiliary relays are abnormal. Continue V 0054 The latched counters are abnormal. Continue V 0055 The latched 32-bit counters are abnormal. Continue V 0056 The latched special auxiliary relay is abnormal. Continue V 0059 The latched data registers are abnormal. Continue V 005D The CPU module does not detect a memory card. Continue V 005E The memory card is initialized incorrectly. Continue V 0063 An error occurs when data is written to the memory card. Continue V 0064 A file in the memory card cannot be read.

Continue V 0070 The actual placement of the function cards is not consistent with the settings. Stop V 0102 The interrupt number exceeds the range. Stop V 0202 The MC instruction exceeds the range. Stop V 0302 The MCR instruction exceeds the range. Stop V 0D03 The operands used in DHSCS are not used properly. Stop V 0E05 The operands HCXXX used in DCNT are not used properly. Stop V 1300 - 130F Errors occurred in the remote modules Continue V 1402 The arrangement of the I/O modules is not consistent with the settings. Stop V 140B Number of communication modules exceeds the limit of four. Stop V 140D Number of extension modules exceeds the limit of 32.

Stop V 140E Number of remote modules exceeds the limit of eight on the right side of the CPU module. Stop V 1500 Connection lost in the remote modules Continue V 1502 - 150F Errors occurred in the remote modules Continue V 1600 The ID of the extension module exceeds the range. Stop V 1601 The ID of the extension module cannot be set. Stop V 1602 The ID of the extension module is duplicated. Stop V 1603 The extension module cannot be operated. Stop V 1604 Extension module communication timeout Stop V 1605 Hardware failure Stop V 1606 Errors on the communication module function card Stop V