Chapter 12 Troubleshooting 12.4.2 Error Codes and LED Indicators for Analog/Temperature Modules 12_ *1: The errors are specified as warnings to ensure the CPU module can still run even when the warnings are triggered by its AIO modules. Set up HWCONFIG to have the following first 4 error codes appear as errors when they occur. 12.4.3 Error Codes and LED Indicators for Positioning Module AS02 / 04PU 12-33 Error code Description ERROR LED indicator status A D / ERROR D A / A ↔D 16#1605 Hardware failure OFF ON 16#1607 The external voltage is abnormal. OFF ON 16#1608 The factory calibration or the CJC is abnormal. OFF ON 16#1801*1 The external voltage is abnormal.
OFF Blinking 16#1802*1 Hardware failure OFF Blinking 16#1804*1 The factory calibration is abnormal. RUN: Blinking STOP: OFF Blinking 16#1807*1 The CJC is abnormal. OFF Blinking 16#1808 The signal received by channel 1 exceeds the range of analog inputs (temperature). RUN: Blinking STOP: OFF Blinking 16#1809 The signal received by channel 2 exceeds the range of analog inputs (temperature). 16#180A The signal received by channel 3 exceeds the range of analog inputs (temperature). 16#180B The signal received by channel 4 exceeds the range of analog inputs (temperature). 16#180C The signal received by channel 5 exceeds the range of analog inputs (temperature).
16#180D The signal received by channel 6 exceeds the range of analog inputs (temperature). 16#180E The signal received by channel 7 exceeds the range of analog inputs (temperature). 16#180F The signal received by channel 8 exceeds the range of analog inputs (temperature). - When power-on, the module is not detected by CPU module. OFF Blinking once or twice and after 2 seconds, it blinks repeatedly Error code Description ERROR LED indicator status A D ERROR 16#1802 Hardware failure OFF Blinking