AS Series Operation Manual 12.4.4 Error Codes and LED Indicators for High Speed Counter Module AS02HC _12 12.4.5 Error Codes and LED Indicators for Load Cell Module AS02LC *1: The following errors are specified as warnings to ensure the CPU module can still run even when the warnings are triggered by its AIO modules. You can set up HWCONFIG to have the following first 3 error codes appear as errors when they occur. 12-34 Error code Description ERROR LED indicator status ON Blinking 16#1605 Counted result in the latched area is not retainable (major error) V 16#1606 Module settings in the latced area is not retainable.
(major error) V 16#1607 Module setting error (major error) V 16#1800 Counter overflow / underflow on CH1 V 16#1801 Counter overflow / underflow on CH2 V 16#1802 Linear count exceeding the set upper/lower limit on CH1 V 16#1803 Linear count exceeding the set upper/lower limit on CH2 V 16#1804 The variation in relation to a SSI encoder position exceeding the limit on CH1 V 16#1805 The variation in relation to a SSI encoder position exceeding the limit on CH2 V 16#1806 Abnormal SSI communication on CH1 V 16#1807 Abnormal SSI communication on CH2 V 16#1808 SSI absolute position cross zero point on CH1 V 16#1809 SSI absolute position cross zero point on CH2 V Error code Description ERROR LED indicator status A D ERROR 16#1605 Hardware failure (the diver board included) OFF ON 16#1607 The external voltage is abnormal.
OFF ON 16#1801*1 The external voltage is abnormal. OFF Blinking 16#1802*1 Hardware failure OFF Blinking 16#1807*1 Diver board failure OFF Blinking 16#1808 The signal received by channel 1 exceeds the range of analog inputs or the SEN voltage is abnormal. RUN: Blinking STOP: OFF Blinking 16#1809 The signal received by channel 1 exceeds the weight limit. 16#180A The factory calibration in channel 1 is incorrect. 16#180B The signal received by channel 2 exceeds the range of analog inputs or the SEN voltage is abnormal. 16#180C The signal received by channel 2 exceeds the weight limit. 16#180D The factory calibration in channel 2 is incorrect.