Chapter 12 Troubleshooting 12.4.6 Error Codes and LED Indicators for Module AS04SIL IO-Link as a Communication Module 12_ 12.4.7 Error Codes and LED Indicators for Module AS00SCM as a Communication Module 12.4.8 Error Codes and LED Indicators for Module AS00SCM as a Remote Module 12-35 Error Code Description MS Status LED indicator ON Blinking 16#1605 Hardware failure V 16#1606 24VDC power supply is not sufficient and then recovered from low-voltage for less than 10 ms.
V Error Code Description NS LED indicator ON Blinking 16#1800 Error occurs in IO-Link Master V 16#1801 Error occurs in IO-Link device V 16#1802 No external power supply V Error Code Description ERROR LED indicator status ON Blinking 16#1605 Hardware failure V 16#1606 The setting of the function card is incorrect. V 16#1802 Incorrect parameters V 16#1803 Communication timeout V 16#1804 The setting of the UD Link is incorrect. V Error Code Description ERROR LED indicator status ON Blinking Blinking fast 16#1301 Hardware failure V 16#1302 The setting of the function card is incorrect.
V 16#1303 24 VDC power supply is not sufficient and then is recovered from a low-voltage less than 10ms situation. V 16#1502 Incorrect parameters V 16#1503 Extension module communication timeout V