AS Series Operation Manual 12.4.9 Error Codes and LED Indicators for Module AS01DNET (Master/Slave Mode) _12 12-36 Code Explanation Correction 0~63 Node address of AS01DNET-A (in normal operation) -- 80 AS01DNET-A is in STOP status. Turn the PLC to RUN and start I/O data exchange F0 The node ID of AS01DNET is the same as that of other node or exceeds the allowed range. 1. Ensure that the node address of AS01DNET is unique. 2. Re-power AS01DNET. F1 No configured slave in Scan List. Configure the scan list and then download the configuration to AS01DNET. F2 Too low voltage of the work power Check if the power supply for AS01DNET and the PLC is normal.
F3 AS01DNET enters the test mode Switch the function switch IN1 from On to Off and re-power AS01DNET-A. F4 BUS-OFF 1. Check if the network cable is normal and the shielded cable is grounded. 2. Check if the baud rates of all nodes in the network are same. 3. Check if the start and end of the network cable are both connected with a 121Ω terminal resistor. 4. Re-power AS01DNET-A. F5 No network power 1. Check if the network cable is normal. 2. Ensure that the network power is normal. F6 Internal error; Flash or RAM check error If the error still exists after re-power, send AS01DNET-A back for repair.
F8 Error produced in factory manufacturing If the error still exists after re-power, send AS01DNET-A back for repair. F9 Internal error; EEPROM access failure If the error still exists after re-power, send AS01DNET-A back for repair. FA Invalid configuration data 1. Configure the network correctly and re-download it to AS01DNET- A. 2. Check if the node address of one slave in the scan list is the same as that of AS01DNET-A. E0 Identification parameters returned from the slave do not match the configuration data. 1. Check if there is any change in node ID of the slave in the network. 2. Check if some node device in the network is replaced. 3. Re-configure the network.
E1 I/O Data size returned does not match that in the scan list. Re-configure I/O data size of the slave, download the configuration to AS01DNET-A and run the PLC. E2 The slave device in the scan list does not exist or is offline when AS01DNET-A is in master mode. 1. Check if there is a change in the node address of the slave. 2. Check if the communication cable is disconnected or connected loosely. 3. Check if the bus cable length exceeds the maximum transmission distance. If so, the system may not be stable. The I/O connection between the slave AS01DNET-A and the master is broken when AS01DNET-A is in slave mode. E3 AS01DNET-A fails to transmit data. 1.
Make sure that the connection between AS01DNET-A and the network is normal.