Delta Electronics — 12.4.10 Error Codes and LED Indicators for Module AS01DNET (RTU Mode)

Chapter 12 Troubleshooting 12_ 12.4.10 Error Codes and LED Indicators for Module AS01DNET (RTU Mode) 12-37 Code Explanation Correction 2. Check if the baud rate of AS01DNET-A is the same as that of other node in the network. E4 Error detected in sequence of fragmented I/O data from the slave device. Check if the slave is operating normally. E5 The slave device returns error when AS01DNET-A attempts to communicate with it. Check if the slave is operating normally. E6 IO data size returned from the slave is bigger than that configured in Scan List. Check that the IO data size of the slave should be the same as that configured in Scan List. E7 AS01DNET-A is checking MAC ID.

If the code is displayed long, do the troubleshooting according to the following steps. 1. Make sure that at least two nodes work normally in the network. 2. Check if either end of the network is connected with the terminal resistor of 121Ω. 3. Check if the baud rates of the node devices in the network are same. 4. Check if the communication cable is normal so as to avoid that the cable is disconnected or connected loosely. 5. Check if the bus cable length exceeds the maximum transmission distance. If so, the system may not be stable. 6. Check if the shielded wire of the network cable is grounded. 7. Re-power AS01DNET-A scanner module.

Code Indication How to deal with 0~63 Node ID of the scanner module (When in RUN state) No correction needed F0 The node ID is repeated or exceeds allowed range. 1. Ensure that the node ID of AS01DNET (RTU) is unique in the DeviceNet network within the range of 0~63. 2. Repower it on after changing the node ID. F1 No I/O module is configured to AS01DNET (RTU) in the DeviceNet Builder software. Add I/O modules in AS01DNET (RTU) in the DeviceNet Builder software and download the configuration data to AS01DNET (RTU) after the configuration is finished. F2 The work voltage of AS01DNET (RTU) is too low. Check if the power supply for AS01DNET (RTU) works normally.

F3 AS01DNET (RTU) enters the test mode. Repower AS01DNET (RTU). F4 AS01DNET (RTU) is the Bus- Off state. 1. Check if the network communication cable is normal and the shielded cable is grounded. 2. Ensure the baud rates of all network nodes are same. 3. Check if the two ends of the network are both connected with a 120Ω terminal resistor. 4. Repower the scanner module.