AS Series Operation Manual _12 12-38 Code Indication How to deal with F5 No network power supply for AS01DNET(RTU) 1. Check if the network cable is normal. 2. Check if the network power supply is normal. (The external 24V DC network power supply is connected between red V+ and black V- of AS01DNET (RTU) .) F6 Internal error; An error in the internal storage units of AS01DNET (RTU) Return the product for repair if the error still exists after re- power on. F7 Internal error; An error in the data exchange units of AS01DNET (RTU) Return the product for repair if the error still exists after re- power on.
F8 Manufacture error Return the product for repair if the error still exists after re- power on. F9 Internal error; An error in the access of the Flash of AS01DNET (RTU) Return the product for repair if the error still exists after re- power on. E4 Module error Check if an error occurs in the modules connected to the right side of AS01DNET (RTU); Check if the module exists; Check if current module matches that configured in the software; Check if the unconfigured module is added. E7 Repeated node ID detection If the code has emerged for a long time, please shoot troubles in the methods below. 1. Ensure that there are at least two nodes working normally in the network. 2.
Check if the two ends of the network are both connected with a 121Ω terminal resistor. 3. Ensure that the baud rates of all network nodes are same. 4. Check if the network cable has a problem such as being disconnected and loosened. 5. Check if the bus communication cable length exceeds maximum transmission distance. If the maximum transmission distance is exceeded, the stability of the system can not be ensured. 6. Check if the shielded wire of the network communication cable is grounded. 7. Turn on the power of AS01DNET (RTU) again. E9 The number of I/O modules connected to AS01DNET (RTU) exceeds the maximum 8. Check if the number of I/O modules connected to AS01DNET (RTU) is more than 8.
80 AS01DNET (RTU) is in STOP state. 1. Check if the RUN/STOP switch of the PLC connected to the DeviceNet master is turned to RUN. 2. Check if the value of control word of AS01DNET (RTU) is 1. For details, refer to section 10.5.4.3.4. 83 The AS01DNET (RTU) configuration in the software is being downloading. Wait until the download of AS01DNET (RTU) configuration data is completed.