AS Series Operation Manual AS06XA-A Electrical specifications _2 Functional specifications for the analog-to-digital conversion *1: If the input signal exceeds the hardware input limit, the module only shows the maximum value. If the input signal is below the lower limit, it only shows the minimum value. *2: If the input signal exceeds the hardware input limit, it also exceeds the conversion limit and a conversion limit error appears. For example in the voltage input mode (-10 V to +10 V), when the input signal is 10.15 V, exceeding the hardware upper limit, it also exceeds the conversion upper limit.
The module uses the upper limit value (32384) as the input signal and a conversion limit error appears. *3: If an input signal exceeds the absolute range, it might damage the channel. 2-39 Module name AS06XA-A Number of Inputs: four; Outputs: two inputs/outputs Analog-to-digital Voltage input/Current input; Voltage output/Current output; conversion Supply voltage 24 VDC (20.4 VDC–28.8 VDC) (-15% to +20%) Connector type Removable terminal block Conversion time 2ms/channel An analog circuit is isolated from a digital circuit by a digital integrated circuit/an optocoupler, but the analog channels are not isolated from one another. Isolation between a digital circuit and a ground:
500 VDC Isolation between an analog circuit and a ground: 500 VDC Isolation between an analog circuit and a digital circuit: 500 VDC Isolation between the 24 VDC and a ground: 500 VDC Isolation Weight 145 g Analog-to-Digital Voltage Input Conversion Rated Input Range -10 V ~ +10 V 0 V ~ 10 V ±5 V 0 V ~ 5 V 1 V ~ 5 V K-32000 ~ K32000 K0 ~ K32000 K-32000 ~ K32000 K0 ~ K32000 K0 ~ K32000 Rated Conversion Range -10.12V ~ 10.12V -0.12V ~ 10.12V -5.06V ~ 5.06V -0.06V ~ 5.06V 0.95V ~ 5.05V Hardware Input Limit*1 K-32384 ~ K32384 K-384 ~ K32384 K-32384 ~ K32384 K-384 ~ K32384 K-384 ~ K32384 Conversion Limit*2 Error Rate Room Temperature: ±0.2% ; Full Temperature Range:
±0.5% Hardware Resolution 16 bits Input Impedance 2MΩ Absolute Input Range*3 ±15 V