Delta Electronics — 2.4.1 General Specifications

AS Series Operation Manual _2 2-41 Digital-to-Analog Current Output Conversion Rated Output Range 0–20 mA 4–20 mA K0 ~ K32000 K0 ~ K32000 Conversion Range Hardware Output Range -0.2 mA to 20.2 mA 3.8–20.2 mA Error Range ±0.2% (Room Temperature) Error Range ±0.5% (Full Temperature Range) Linearity Error ±0.03% (Room Temperature) Linearity Error ±0.10% (Full Temperature Range) Hardware Resolution 12 bits Permissible Load ≦550 Ω Impedance